STS GasAssistTIGHTNESS & PURGE CALCULATOR
Step 1 of 4

Pipework and meter

Choose each pipe size, enter the length and select the meter.

Reference values and calculation notes

Choose the actual pipe material and nominal size, then enter its measured length. The reference volume per metre is filled in automatically. Add every run in the section being tested; use a verified manufacturer value for unlisted pipework. STS must check these preset reference values against its final licensed Edition 4 copy before live use.

Pipe type and sizeLength (m)Pipe volume
Reference values and calculation notes

The metric/imperial choice describes the meter register. A listed meter fills in its internal capacity in m³ regardless of the register type. For any other meter use verified manufacturer data in m³, never the cumulative consumption reading. Where actual valves and fittings volume is known, enter that value. Otherwise, the 10% fallback is applied to the calculated pipework volume. The selected amount is added to pipe and meter volumes. Select “No meter” when excluded and enter 0.

Draft saved on this device as you work.
Step 1 of 4

Prototype for STS review · Reference values require verification before live use.

Quick answers

Using STS GasAssist on site

What is the new tightness testing procedure?

Under IGEM/UP/1B Edition 4, follow the prescribed let-by check, stabilisation and two-minute tightness test at the appropriate fuel-gas pressures.

Existing installations with existing appliances connected: a pressure drop may be acceptable only where there is no reported smell of gas. The allowance is based on the total installation volume being tested and the fuel gas, rather than the meter type alone.

Natural gas allowances: installation volume up to 0.005 m³: 8 mbar; over 0.005 to 0.010 m³: 4 mbar; over 0.010 to 0.015 m³: 2.5 mbar; over 0.015 to 0.035 m³: 1 mbar. LPG and LPG/Air have different limits.

The pipework must be gas tight: any perceptible drop within the allowance requires all appliances to be isolated and the pipework and meter retested with no perceptible movement. If an appliance cannot practicably be isolated, test with it connected and apply the same no-perceptible-movement requirement. A drop above the allowance, or perceptible movement on the retest, requires the escape to be traced and repaired or the installation made safe.

New installations, only new appliances connected, or pipework-only tests: there is no appliance-leakage allowance. The requirement is no perceptible movement, assessed using the applicable gauge criterion.

Before completing the outcome, reinstate as appropriate, check disturbed joints and pipework between isolation valves and appliances with LDF, and confirm no smell of gas. Any accepted appliance-related drop also requires a satisfactory site-specific risk assessment. Follow the full current controlled standard; GasAssist supports the engineer’s assessment.

Why use this app?

It brings pipe and meter volume, test readings and purge planning into one guided working note. It helps with the arithmetic and prompts checks; the engineer still assesses the installation and follows the current procedure.

What are the permissible pressure drops for LPG/Air and LPG?

LPG/Air mixtures and LPG use different Edition 4 tables. Select the actual fuel gas; these are maximum drops over the prescribed two-minute test for existing installations with existing appliances connected and no reported smell of gas.

LPG/Air — Table 2

Installation volume (m³)Maximum drop
Up to and including 0.0251.5 mbar
Over 0.025, up to and including 0.0350.5 mbar

LPG — Table 5

Installation volume (m³)Maximum drop
Up to and including 0.00252 mbar
Over 0.0025, up to and including 0.0051 mbar
Over 0.005, up to and including 0.0100.5 mbar
Over 0.010, up to and including 0.035No perceptible movement

A drop within an allowance does not complete the pass. Any perceptible drop requires appliance isolation and a pipework/meter retest with no perceptible movement. If isolation is impracticable, leave the appliance connected and require no perceptible movement. Complete the prescribed final checks.

New installations, only new appliances connected, and pipework-only tests require no perceptible movement. Use the fuel-specific test pressure and full current controlled procedure. Source: Gas Safe Register ISU 133 Edition 2, 15 April 2026.

Can I use it without a phone signal?

Yes. Open the app on this device while connected and submit your contact details if prompted. Keep “Remember me on this device” ticked and let the page load. The calculator and drafts then work offline. Contact submission and the admin area need a connection.

What if the installation is outside the app’s scope?

This version is for domestic installations up to 0.035 m³. If the volume exceeds that limit, it stops the pressure-drop assessment. The engineer must select the appropriate procedure for the installation.

Where is my work saved?

Draft job entries stay in this browser on this device. Use “Print working note / save PDF” or “Export calculation data” to keep a separate copy. Clear the job when finished. Contact details submitted through the welcome form are held separately by STS.

Welcome to STS GasAssist

Enter your name and email, then tap Save and continue below. Marketing emails are optional.

Enter your details once on this device to use the free Tightness & Purge Calculator.

You can unsubscribe at any time. Your details are saved in STSAssist contacts for authorised STS staff. If you opt in and STS connects its Brevo account, your first name and email are sent to Brevo. Read how STS uses your details.